ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 3 – May 2011
Modbus Parameters
Page 109
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Record Alarm 3
Status
7580
0x1D9C
R/W
Value
Record Change Of State For Alarm 3
0
Do Not Record Alarm 3
1
Record Alarm 3
Record Alarm 4
Status
7581
0x1D9D
R/W
Value
Record Change Of State For Alarm 4
0
Do Not Record Alarm 4
1
Record Alarm 4
Record Alarm 5
Status
7582
0x1D9E
R/W
Value
Record Change Of State For Alarm 5
0
Do Not Record Alarm 5
1
Record Alarm 5
Record Power
7583
0x1D9F
R/W
Value
Record Power Turned On/Off
0
Do Not Record Power On/Off
1
Record Power On/Off
Trigger Recording
On Alarm 1
7584
0x1DA0
R/W
Value
Alarm 1 To Trigger Recording
0
Off
1
Trigger On Alarm 1 (
if trigger is alarm
)
Trigger Recording
On Alarm 2
7685
0x1DA1
R/W
Value
Alarm 2 To Trigger Recording
0
Off
1
Trigger On Alarm 2 (
if trigger is alarm
)
Trigger Recording
On Alarm 3
7686
0x1DA2
R/W
Value
Alarm 3 To Trigger Recording
0
Off
1
Trigger On Alarm 3 (
if trigger is alarm
)
Trigger Recording
On Alarm 4
7687
0x1DA3
R/W
Value
Alarm 4 To Trigger Recording
0
Off
1
Trigger On Alarm 4 (
if trigger is alarm
)
Trigger Recording
On Alarm 5
7688
0x1DA4
R/W
Value
Alarm 5 To Trigger Recording
0
Off
1
Trigger On Alarm 5 (
if trigger is alarm
)
Sample Size
7595
0x1DA5
RO
Size in bytes, for current setup of recording sample
Record Event 1
7599
0x1DAF
R/W
Value
Record Change Of State For Event 1
0
Do Not Record Event 1
1
Record Event 1
Record Event 2
7600
0x1DB0
R/W
Value
Record Change Of State For Event 2
0
Do Not Record Event 2
1
Record Event 2
Record Event 3
7601
0x1DB1
R/W
Value
Record Change Of State For Event 3
0
Do Not Record Event 3
1
Record Event 3
Record Event 4
7602
0x1DB2
R/W
Value
Record Change Of State For Event 4
0
Do Not Record Event 4
1
Record Event 4
Record Event 5
7603
0x1DB3
R/W
Value
Record Change Of State For Event 5
0
Do Not Record Event 5
1
Record Event 5