ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 3 – May 2011
Modbus Parameters
Page 87
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Scale Point 13
1078
0x0436
R/W
>Scale point 12 to 100.0%
Display Point 13
1079
0x0437
R/W
Valid between scale range maximum and minimum
Scale Point 14
1080
0x0438
R/W
>Scale point 13 to 100.0%
Display Point 14
1081
0x0439
R/W
Valid between scale range maximum and minimum
Scale Point 15
1082
0x043A
R/W
>Scale point 14 to 100.0%
Display Point 15
1083
0x043B
R/W
Valid between scale range maximum and minimum
Option Slot A Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Digital Input A Status 2115
0x0845
RO
Value
Digital Input A Status
0
Inactive
1
Active
Option Slot A
Module Type
2116
0x0844
RO
Value
Module Fitted In Slot A
0
None Fitted
1
RS485 Communications
3
Digital Input
4
Auxiliary Input A
5
Ethernet Communications
255
Error (
unrecognised module
)
RS485 Address
2117
0x0845
R/W
Value
RS485 Address
0
Modbus Master mode
1 to 255
Modbus Slave Address
RS485 Data Rate
2118
0x0846
R/W
Value
Baud Rate
0
4800
1
9600
2
19200 (
Default
)
3
38400
4
57600
5
115200
RS485 Parity
2119
0x0847
R/W
Value
Parity
0
None
1
Even
2
Odd
Auxiliary Input A
Type
2120
0x0848
R/W
Value
Auxiliary A Input Type
0
0 to 20mA DC
1
4 to 20mA DC
2
0 to 10V DC
3
2 to 10V DC
4
0 to 5V DC
5
1 to 5V DC
Target Setpoint
Address
2121
0x0849
R/W
Target setpoint parameter address for master mode