ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
Page 110
Modbus Parameters
59407, Issue 3 – May 2011
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Memory Used
7605
0x1DB5
RO
Recorder Memory Used. 0 (
Empty
) to 100% (
Full
)
Date format
7868
0x1EBC
R/W
Value
Display Date Format
0
dd/mm/yyyy (European Default)
1
mm/dd/yyyy (USA Default)
Time
7869
0x1EBD
R/W
Format is the number of seconds since midnight.
Date
7870
0x1EBE
R/W
Format 6 digits. Example 280308 for 28/03/2008
Real Time Clock
Fitted
7871
0x1EBF
RO
Value
Real Time Clock Fitted
0
Not Fitted
1
Fitted
Day Of The Week
7872
0x1EC0
R/W
Value
Day Of Week
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
Display Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
LED 1 Label
7660
0x1DEC
R/W
5 ASCII characters, which can re read or written using
Modbus functions 16 or 23. Valid characters are 0 to
9, a to z, A to Z, plus ( ) - and _.
Defaults: 1 = PRI (Primary); 2 = SEC (Secondary);
3 = TUNE (Tuning); 4 = ALARM (Alarm)
LED 2 Label
7661
0x1DED
R/W
LED 3 Label
7662
0x1DEE
R/W
LED 4 Label
7663
0x1DEF
R/W
LED 1 Usage
7664
0x1DF0
R/W
Value
LED 1 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2