ProVU4 Controller, Profiler & Recorder/Controller - Product Manual
59407, Issue 3 – May 2011
Modbus Parameters
Page 107
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Alarm 4 Inhibit
Status
6197
0x1835
RO
Value
Alarm 4 Inhibit Status
0
Not Inhibited
1
Inhibited
Alarm 5 Type
6208
0x1840
R/W
Value
Alarm 1 Type
0
Not Used
1
Process High Alarm
2
Process Low Alarm
3
Deviation Alarm (SP-PV)
4
Band Alarm
5
Loop Alarm
6
Input/Sensor Break Alarm
7
Auxiliary Input A Break Alarm
8
Auxiliary Input B Break Alarm
Alarm 5 Value
6209
0x1841
R/W
Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis
6210
0x1842
R/W
Limited by the input span
Alarm 5 Inhibit
Enable/disable
6211
0x1843
R/W
Value
Alarm 5 Inhibit Enable
0
Disabled
1
Enabled
Alarm 5 Status
6212
0x1844
RO
Value
Alarm 5 Status
0
Inactive
1
Active
Alarm 5 Inhibit
Status
6213
0x1845
RO
Value
Alarm 5 Inhibit Status
0
Not Inhibited
1
Inhibited
Recorder & Clock Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Recording Sample
Interval
7550
0x1D7E
R/W
Value
Recording Sample Interval
0
Every Second
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
11
Every 30 Minutes