position 3 of profile 1 the segment number will be 3, and to edit or insert a segment at
position 3 of profile 6 the segment number will also be 3.
Creating, Editing or Inserting Segments - Request (
to instrument
)
Field Name
Data
Comments
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
11 or 12
0B or 0C
Create Segment (WS) = 11dec / 0x0Bhex
Insert Segment (IS) = 12dec / 0x0Chex
Edit A Segment (ES) = 12dec / 0x0Chex
Byte Count
22 or 24
16 or 18
Create Segment (WS) = 22dec / 0x16hex
Insert Segment (IS) = 24dec / 0x18hex
Edit A Segment (ES) = 24dec / 0x18hex
Command Code High Byte
87, 73 or
69
57 or 49
Create Segment (WS) = 87dec / 0x57hex
Insert Segment (IS) = 73dec / 0x49hex
Edit A Segment (ES) = 69dec / 0x45hex
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Position High Byte
A/R
A/R
Note: The Segment Position is not
included in the message when creating
a segment at the next available position.
Segment Position Low Byte
A/R
A/R
Segment Type High Byte
00
00
0 = Ramp Time, 1 = Ramp Rate,
2 = Step, 3 = Dwell, 4 = Hold, 5 = Loop
6 = Join, 7 = End, 8 = Repeat sequence
then end
Segment Type Low Byte
A/R
A/R
Segment Info A (Byte 4 - High)
Floating point number
The meaning of the data contained in
Segment Info A depends on the type of
segment it relates to. See below.
Segment Info A (Byte 3)
Segment Info A (Byte 2)
Segment Info A (Byte 1 - Low)
Segment Info B (Byte 4 - High)
Floating point number
The meaning of the data contained in
Segment Info B depends on the type of
segment it relates to. See below.
Segment Info B (Byte 3)
Segment Info B (Byte 2)
Segment Info B (Byte 1 - Low)
Auto Hold Type High Byte
A/R
A/R
0 = Auto-Hold Off, 1 = Hold above SP,
2 = Hold below SP,3 - Hold above and
below SP
Auto Hold Type Low Byte
A/R
A/R
Auto Hold Value (Byte 4 - High)
Floating point number
Auto Hold Value (Byte 3)
Auto Hold Value (Byte 2)
Auto Hold Value (Byte 1 - Low)