![Welbilt Merrychef 32Z3923 Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/welbilt/merrychef-32z3923/merrychef-32z3923_service-and-repair-manual_953836018.webp)
Merrychef eikon
®
e2s service and repair manual
18
_______________________________________________________________________________________________________________________________
_______________________________________________________________________________________________________________________________
2 For your safety
Back to contents >
2.12
Safe working during electrical installation
For your safety
Before starting work, familiarize yourself with the hazards described in section 3.7 ‘For your safety’ in the eikon
®
e2s
Installation and User manual.
Eligibility of personnel for the electrical installation
Only electricians qualified under the terms of EN 50110-1 and from an authorized service company are permitted to perform
work on electrical equipment.
Regulations for the electrical installation
Observe the following requirement to prevent hazards caused by faulty electrical connections:
§
The electrical supply must be connected in accordance with applicable local and national regulations and regulations
of the professional associations and of the relevant power supply company.
Personal protective equipment
Wear the personal protective equipment specified in section 2.3 'Personal protective equipment'.
Live components
DANGER
Risk of electric shock from live parts
When the appliance is not connected to an equipotential bonding system, there is a risk of electric shock from touching live
parts.
§
Make sure that any work on the electrical system is performed solely by a qualified electrician from an authorized
service company.
§
Make sure that the electrical connections are intact and connected securely before putting the appliance into use.
§
Before preparing the appliance for use, make sure that the appliance, including all metallic accessories, is connected
to an equipotential bonding system.
Residual-current device (RCD) The installation regulations require protection by a residual-current device (RCD). Suitable
residual-current devices meeting the relevant national regulations must be used.
If the installation includes more than one appliance, one residual-current device must be
provided for each appliance.
Disconnection device
An easily accessible all-pole disconnection device with a minimum contact separation of 3
mm must be installed close to the appliance. The appliance must be connected via this
disconnection device.
The disconnection device is used to disconnect the appliance from the electrical supply
for cleaning, repair and installation work.
Fitted frequency-converter
The appliance is fitted with one frequency converter (FC) and EMC mains input filters.
These devices may result in a leakage current of more than 3.5 mA per FC drive. Use a suitable RCD for the rated voltage.
Properties of the residual-current device
The residual-current device (RCD) must have the following properties:
§
Filter for filtering out RF currents
§
“Time delayed" trip characteristic for RCD devices with trip threshold of 30mA*: prevents RCD being tripped by
charging currents of capacitors and parasitic capacitances when appliance is switched on.
§
“Leakage current protection, type SI” trip characteristic for RCD devices with trip threshold of 30mA*: insensitive to
nuisance tripping.
§
*Local national regulations may require lower trip ratings, such as in North America. In which case these lower trip
threshold ratings must be adopted, ensuring the dedicated device has a high immunity to nuisance tripping.
Note. Residual Current Devices (RCDs) are also known by other terms, such as Earth Leakage Circuit Breakers (ELCBs), Safety
Switches, Ground Fault Interrupters (GFIs) and Ground Fault Circuit Interrupters (GFCIs). These should not be confused with
over current protection.