14
E. Gas Supply
Post instructions to be followed if the user smells gas.
Display the instructions in a prominent location.
Obtain the instructions from the local gas supplier.
1.
Gas Supply Requirements
•
Gas supply type MUST match the type of gas shown on the rating plate.
•
Gas supply pressure must NOT exceed 14” water column (1/2 psi), and fall within the
pressure range shown below when using 3/4” NPT line and a 1/2” NPT connection
o
Na
tural gas pressure at 1000 BTU/CF must be 5 1/2” – 14” water column.
o
Propane gas pressure must be between 11” – 14” water column.
•
If the gas or propane supply pressure exceeds 14” water column, a pressure regulating valve
(pressure regulator) must be installed in the gas supply line to reduce pressure to this
appliance. See Figure 3-2.
2.
Gas Supply Line Requirements
The Installer/Owner is responsible for furnishing and installing gas supply lines, valves,
regulators, and accessories.
When installing gas supply lines and accessories, observe the following:
a.
Refer to Figure 3-2 for the recommended layout of the gas supply lines.
b.
Use non-hardening pipe thread sealant resistant to LP gas.
c.
The ¾” NPT gas inlet is on the bottom of the 24CGA10. See Figure 3-2
d.
Install main manual shut off valve between the gas supply and the appliance. See Figure 3-2.
This main manual shut off valve is called the “Main Manual Gas Valve.”
e.
Install a sediment trap (drip leg) in gas supply line. See Figure 3-2.
3.
Test Gas Supply Lines
a.
Check all connections for proper tightness.
b.
Remove the control side panel to inspect internal gas connections. Do not replace the panel
until installation is complete.
c.
Open the gas supply valves.
24
CGA
10
GAS MANIFOLD
CONNECTION
DRIP LEG
MAIN GAS
SUPPLY
MAIN MANUAL
GAS VALVE
PRESSURE REGULATING
VALVE (IF REQUIRED)
Gas Supply Line Layout
Figure 3-2