15
NOTICE
The use of good quality feed water as listed in the Cleveland Range Limited Warranty is the
responsibility of the Owner-User.
See Water Quality Recommendations as listed in the Cleveland Range Limited Warranty.
THE USE OF POOR-QUALITY FEED WATER WILL VOID EQUIPMENT WARRANTIES.
d.
Check all lines and connections for leaks, both inside and outside this appliance, with soap
and water solution.
e.
All leaks must be corrected before attempting to operate this appliance.
4.
Pressure Test Gas Supply Lines
If pressure testing is required, this appliance must be disconnected or isolated from the gas
supply piping system during pressure testing as follows:
•
The appliance and its individual shutoff valve (Main Manual Gas Valve) must be
disconnected
from the gas supply piping system during any pressure testing of that system
at test pressures in excess
of 1/2 psi (14” water column or 3.45 kPa).
•
The appliance must be
isolated
from the gas supply piping system by closing its individual
manual shutoff valve (Main Manual Gas Valve) during any pressure testing of the gas supply
piping system at test pressure
s equal to or less than 1/2 psi (14” water column or 3.45 kPa).
F. Water Supply
1.
Water Supply Quality Requirements
a.
Contact Cleveland Range for details on how to provide water per Minimum Water Quality
Requirements in the Warranty, or how to increase the frequency of maintenance, cleaning,
and descaling.
b.
Poor water supply quality degrades performance.
c.
Check the quality of supply water before designing the water supply by contacting a local
water treatment specialist for on-premises water analysis.
d.
Softened or chlorinated water damages the steam generator by increasing corrosion. Carbon
type filters are required before water enters the steam generator if supply water is softened or
chlorinated.
e.
If a water treatment system must be installed to achieve acceptable water quality, install it
BEFORE
connecting the water supply lines.
f.
If analysis shows that supply water is below Minimum Water Quality:
•
a water treatment system and/or carbon filter must be installed in the line feeding the
steam generator.
2.
Connect the Water Supply Lines
•
The Installer/Owner is responsible for the water connection of this appliance.
•
This appliance is to be installed to comply with all applicable federal, state, or local plumbing codes.
•
Connect this appliance to COLD WATER
The condenser system and steam generator will
not work properly if they are connected to HOT or WARM water.
a.
Water supply must have a minimum dynamic (flow) pressure of 35 psi (2.4 kg/cm²) and
a maximum static pressure of 60-psi (4.1 kg/cm²).