6.5.31 Set room thermostat#1 ... 8
Parameter Room thermostat#1 … 8 is display, when parameter
318
has been set to
Room
or
External/Room
.
The heating circuit switches off when the room setpoint value is exceeded by the
switch differential set.
Setting range
Off
Room thermostat function off
Day Off
Function only in setback operation with switch differen-
tial of 1 K.
1.0K
…
3.0K
Switch differential for switch-off
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Control behaviour
.
✓
Menu
Control behaviour
is displayed.
▶
Press function key
Room ther#1
.
✓
Parameter
Room ther#1
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
Control behaviour
Construction
light
Room ther#1
1.0K
Room ther#2
Off
End
-
+
Room ther#1
505
End
Standard
OK
1.0K
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
78-106