6.5.36 Set DHW boost
DHW loading is only possible, if the boiler temperature is higher than the DHW set-
point. The boiler temperature (supply) for DHW loading is determined from the DHW
setpoint and the DHW boost. If a lower value is set, the DHW loading time increases.
If a higher value is set, the DHW loading time decreases, which is detrimental to the
condensate utilisation.
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
DHW
.
✓
Menu
DHW
is displayed.
▶
Press function key
DHW boost
.
✓
Parameter
DHW boost
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
01
DHW
DHW maximum
60.0°C
DHW switch diff
-3.0K
DHW boost
15.0K
End
-
+
DHW boost
603
End
Standard
OK
15.0K
10.0K - 30.0K
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La