6.5.22 Set WTC delay
For installations with high heat exchanger ratings (WTC-GB) without hydraulic de-
couple the boiler start can be delayed. During the delay time the mixer opens and the
boiler has a flow prior to starting.
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
WTC delay
.
✓
Parameter
WTC delay
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
03
Setting #2
max pump speed
100%
VSD variable
Level
WTC delay
30s
End
-
+
WTC delay
430
End
Standard
OK
30s
00s - 240s
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
62-106