6.5.14 Set maximum supply temperature
This parameter limits the heat demand to the maximum supply temperature.
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
Supply max
.
✓
Parameter
Supply max
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
01
Setting #2
Supply min
8.0°C
Supply max
75.0°C
DHW operation
Priority
End
-
+
Supply max
462
End
Standard
OK
8.0°C - 82.0°C
75.0°C
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
54-106