6.5.33 Set room factor-P
The higher the value set, the more influence the room temperature will have on the
supply setpoint formation.
Parameter is only displayed, if parameter
315/316 Control type#1/Control
type#2
is set to
Room
or
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Control behaviour
.
✓
Menu
Control behaviour
is displayed.
▶
Press function key
Room factor-P
.
✓
Parameter
Room factor-P
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
03
Control behaviour
Room factor-P
05
End
-
+
Adaption#1
Off
Room factor-P
508
End
Standard
OK
01 - 20
05
Installation and operating instruction
Remote control station WCM-FS 2.0 and extension module WCM-EM 2.1
6 Operation
83277502 • 3/2012-10 • La
80-106
Содержание WCM-EM 2.1
Страница 107: ...83277502 3 2012 10 La ...