6.5.16 Set boiler mixer circuit boost
Only on heating circuit with mixer (supply sensor B6 fitted to WCM-EM).
This parameter is used to adjust ratings losses. If the mixer circuit boost is too great
this will have a detrimental effect on the benefits of condensing technology.
▶
Activate heating engineer level (see Ch. 6.5).
▶
Press function key
Heating circuit
.
▶
Press function key
Setting #2
.
✓
Menu
Setting #2
is displayed.
▶
Press function key
Boil.MC boost
.
✓
Parameter
Boil.MC boost
is displayed.
▶
Set value using the dial knob and save with function key
OK
.
02
Setting #2
Boil.MC boost
2.0K
Mixer parameter 8.0K
min pump speed
50%
End
-
+
Boil.MC boost
464
End
Standard
OK
2.0K
0.0K - 20.0K