Auto-Zone Plus
Section 3
Programming
3-39
Setpoint Screen #8
Setpoint Screen #9
CVAHU Setpoints
Fan Mode.: Constant
Economizer: Enabled
Use Left/Right Arrow
Line 2 -
The CVAHU can operate the fan in one of two
modes:
Continuous or Constant
running during
occupied hours.
Cycle
with heating or cooling during occupied
hours.
The fan always cycles with heating or cooling
during unoccupied hours.
The Left/Right Arrow keys will toggle the current
setting to the opposite mode.
Line 3 -
The CVAHU has the ability to control the
Economizer operation. If you require this feature,
select Enabled, otherwise, select Disabled.
CVAHU Setpoints
Uses Schedule #: 0
0 = Internal Clock
1-7 = External Clock
The CVAHU normally uses its own
Real Time Clock
and an
Internal Week Schedule
to determine the
Occupied/Unoccupied mode of operation. The CVAHU does
have the ability to use a Global Broadcast from another
scheduling device on the communications loop if a more
powerful schedule is required. If an external schedule is used,
the range of schedule numbers is one to seven.
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...