Auto-Zone Plus
Section 4
Start-Up and Troubleshooting
4-11
1.3.4
Checking the Zone Manager Network Loop
Diagram
Meter Set To Read DC Volts
The indicated readings are typical of a
normally
operating system. Actual readings may vary
slightly due to the number of units installed and other factors. Any significant deviation
from these values generally indicates a problem.
Note:
These tests assume that the CommLink II is connected and powered, and that all
Zone Managers which are connected are also powered.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see
fluctuations on an operating communications loop. The
average
value should be close to the
acceptable range described below.
Values will vary upon initial powerup for about 15-30
seconds as normal communications occur
.
Measurements
LOCAL LOOP
Acceptable Range
T - G (SHLD)
2.9 - 3.1 Volts DC
R - G (SHLD)
1.9 - 2.1 Volts DC
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...