Section 3
Auto-Zone Plus
3-28
Programming
Setpoint Screen #3
Setpoint Screen #4
Setpoint
Screen #5
Cool Staging: 4 Min
Min Cool Off: 4 Min
Heat Staging: 4 Min
Min Heat Off: 4 Min
The heating and cooling stages must have been off for a
minimum amount of time before they can be activated or re-
activated. As each additional stage of heating or cooling is
added, a minimum
Staging Delay period
must be satisfied,
between each additional stage required.
Minimum
Default
Maximum
Cool Staging
1 Min
4 Min
30 Min
Min Cool Off
1 Min
4 Min
30 Min
Heat Staging
1 Min
4 Min
30 Min
Min Heat Off
1 Min
4 Min
30 Min
Heat/Cool Changeover
Interval....: 10 Min
If the Zone Manager needs to change HVAC Modes between
heating and cooling, a
Changeover Delay time
must be
satisfied first. This prevents "Chasing" due to alternate hot and
cold air always being supplied to the zones after short
intervals.
Minimum
Default
Maximum
Interval
1 Min
10 Min
30 Min
Economizer Setpoints
Closed Volts.: 0.0
Opened Volts.: 10.0
If the Zone Manager has been configured for
Economizer
Control
, this screen will appear. The user can set the voltages
required to open and close the damper. Some actuators use a 2-
10 vdc signal instead of 0-10 vdc.
If the system is not configured for Economizer Control, no
economizer setpoint screens will appear.
Minimum
Default
Maximum
Closed Volts
0.0 VDC
0.0 VDC
10.0 VDC
Opened Volts
0.0 VDC
10.0 VDC
10.0 VDC
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...