Auto-Zone Plus
Section 3
Programming
3-3
View/Change Zone
Zone Controller Status
Constant Volume Unit
View/Change
[ Enter Unit ID# ]
Selected Unit: 101
If you have selected the View/Change Zone menu item,
you will be allowed to view any selected zone temperature
and its current cooling and heating setpoints. If you are at
least a Level 1 user, you can also change the cooling and
heating setpoints from this screen. The first screen that
appears, prompts you for the Unit ID you wish to view. The
Unit ID is actually two separate numbers, combined into
one value. The first part of the number contains the Loop
Address at which the zone is located. The second part of
the number contains the actual Board Address.
EXAMPLE: You would like to view the 3rd zone on the
5th loop. Enter 503 as the Unit ID
You would like to view the 12th zone on the
24th loop. Enter 2412 as the Unit ID
Zone Controller
Temperature: 75.4
°
F
Cooling SP.: 75
°
F
Heating SP.: 72
°
F
If the selected Unit ID is correct, and the unit responds, one of
the following screens will appear. If you are a Level 1 user,
you can select either the Cooling or the Heating setpoint with
the Up/Down Arrow keys. To change the setpoint, use the
Left/Right Arrow keys. The setpoints are fully adjustable
between their normal limits of 50 to 90 degrees. When you are
finished viewing this screen, simply press the ESC button to
exit.
Constant Volume Unit
Temperature: 75.4
°
F
Cooling SP.: 75
°
F
Heating SP.: 72
°
F
The Heating Setpoint is never allowed to get any closer than
two degrees of the Cooling setpoint on Zone Controllers and
one degree on Constant Volume Units. If you are lowering the
Cooling setpoint or raising the Heating setpoint, both values
will be kept apart automatically by the correct amount.
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...