Auto-Zone Plus
Section 3
Programming
3-15
Zone Controller Setpoints
Note
The top line always displays the currently selected Zone Controller and the
controller type.
PD ZONE ADDRESS
means a Pressure Dependent Zone is selected.
PI ZONE ADDRESS
means a Pressure Independent Zone is selected.
Setpoint Screen #1
Setpoint Screen #2
PD ZONE ADDRESS 1
OCCUPIED SETPOINTS
Cooling Setpt: 75
°
F
Heating Setpt: 72
°
F
The
Occupied Heating and Cooling Setpoints
are entered on
this screen. The
Heating Setpoint
should always be two
degrees below the
Cooling Setpoint
, or the Zone Controller
will not accept the new values. The System Manager can't
prevent the entry of invalid setpoints. If invalid setpoints are
entered, the previous settings will be retained by the system
and displayed the next time the Zone Setpoints are accessed.
Minimum
Default
Maximum
Cooling Setpoint
50°F
75°F
90°F
Heating Setpoint
50°F
72°F
90°F
PD ZONE ADDRESS 1
UNOCCUPIED SETPOINTS
Cool Setup...:
10
°
F
Heat Setback.:
-10
°
F
The
Unoccupied Heating and Cooling Setback
values are
entered on this screen. The Occupied Cooling Setpoint will be
increased by the Cooling Setback during Unoccupied Mode
and the Heating Setpoint will be decreased by the Heating
Setback.
Minimum
Default
Maximum
Cool Setup
0°F
10°F
30°F
Heat Setback
0°F
-10°F
-30°F
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...