Section 3
Auto-Zone Plus
3-16
Programming
Setpoint Screen #3
NOTE:
If slide
effect is set to 0
°
, the pushbutton override will not function.
Setpoint Screen #4 (Pressure Dependent)
PD ZONE ADDRESS 1
AuxHeat Setpt: 72
°
F
Slide Effect.: 3
°
F
If your Zone Controller has the optional Relay Expansion
Board attached, one of the relays is reserved for an Auxiliary
Heating Relay. Enter that setpoint on the
AuxHeat Setpt
line.
If the relay board is not installed, this line will not be
displayed.
If your Zone Temperature sensor has the optional Setpoint
Adjustment Slide, enter the maximum effect it can have on the
setpoints on the
Slide Effect
line.
Minimum
Default
Maximum
AuxHeat Setpt
50°F
72°F
90°F
Slide Effect
0°F
3°F
5°F
PD ZONE ADDRESS 1
Max Damper....: 100%
Cool Mode Min.: 5%
Heat Mode Min.: 20%
On
Pressure Dependent Zones
, these setpoints are for damper
position, on
Pressure Independent Zones
they are for Airflow
(CFM) values, and the text will change to reflect that.
Minimum
Default
Maximum
PD Zone Max Damper
PI Zone Max Airflow
0 %
0 CFM
100 %
800 CFM
100 %
30000 CFM
PD Zone Cool Mode Min
PI Zone Cool Mode
0 %
0 CFM
5 %
200 CFM
100 %
30000 CFM
PD Zone Heat Mode Min
PI Zone Heat Mode
0 %
0 CFM
20 %
300 CFM
100 %
30000 CFM
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...