Auto-Zone Plus
Section 4
Start-Up and Troubleshooting
4-23
1.3.12
Troubleshooting Checklist
No Zones are Communicating
•
Is the CommLink II connected and plugged in?
•
Are the Zone Manager addresses set to 17?
In an Auto-Zone Plus system all Zone Managers are set to Address = 17.
•
Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.
•
Is the Comm Loop open or shorted?
•
Are the Zone Controller address switches set correctly? See the addressing chart.
•
Are the Zone Controllers powered? Check 24 VAC to the controllers.
•
Is the Network Loop shorted to or connected to any of the Local loops? Check
Network Loop voltages.
•
Is the System Manager connected to a Local loop?
Do not connect the system manager to the network loop!
Some Zones are communicating but others are not:
•
Is the Zone Manager set for the correct number of zones?
•
Are the Zone Controller address switches set correctly? See the addressing chart.
•
Are the Zone Controllers powered? Check 24 VAC to the controllers.
•
Is the REC LED on the missing Zone Controller “flickering”? See Zone Controller
introduction for location of the REC LED.
•
Is the SCAN LED blinking an error code? See the Blink Code chart.
•
Are Comm Loop voltages correct at the missing unit? See the Comm Loop
troubleshooting guide.
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...