Auto-Zone Plus
Section 4
Start-Up and Troubleshooting
4-49
programmable to cover all types of proportional actuators. 0 - 10 VDC or 2 - 10 VDC
outputs are possible.
4.2.4
Relay Output Descriptions
Output #1 -
Main Fan ON/OFF Control
Output #2 -
Mechanical Heating/Cooling Stage #1
Output #3 -
Mechanical Heating / Cooling Stage #2
Output #4 -
Mechanical Heating / Cooling Stage #3
Output #5 -
Mechanical Heating / Cooling Stage #4
Any combination of heating and cooling stages may be configured during setup as long
as the required number of outputs does not exceed four. If heat is used, Output #2 will be
the first stage of heat, cooling stages will be after the heat.
4.2.5
RS-485 Communications Connector
This connector provides the connection point for the Local Loop RS-485
communications loop. The wiring consists of a twisted pair of wires with a shield.
T - RS-485 (+)
Communications terminal
SHLD
- Common return wire, this point is tied to GND on the CV Controller.
R - RS-485 (-)
Communications terminal
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...