Auto-Zone Plus
Section 3
Programming
3-21
Zone Manager Status
Line 1 Displays the currently selected Zone Manager and its current operating software
version on all Status Screens shown below.
Status Screen #1
Status Screen #2
Manager # 1 vl.xx
Occupied Mode
Vent Mode
Line 2 -
Unoccupied Mode
Occupied Mode
Push Button Override
Forced Occupied
Forced Unoccupied
Forced Fan Only Mode
Purge Mode
Line 3 -
Neutral Mode
Vent Mode
Cooling Mode
Heating Mode
Line 4 -
Binary Contact Alarm
Blank Line if no Alarm
Manager # 1 vl.xx
Supply Air: 78.6
°
F
Return Air: 77.3
°
F
Outdoor Air: 70.2
°
F
The
Supply Air Temperature, Return Air Temperature
and
Outdoor Air Temperature
are displayed on this screen.
The Outdoor Air Temperature is either the onboard sensor
reading, or it can be the Global Broadcast value received from
another unit. Only one unit per system needs to have the
Outdoor Air Sensor installed.
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...