Auto-Zone Plus
Section 2
Design Guide
2-7
Zone Manager Addressing
SET THE ADDRESS
SWITCH LIKE THIS
( ADDRESS = 17 )
ALL ZONE MANAGERS MUST
BE SET TO ADDRESS 17
SET EACH ZONE MANAGERS
CLUSTER ADDRESS IN SEQUENCE
( ADDRESS = 1 SHOWN FOR FIRST UNIT )
EACH ZONE MANAGER MUST HAVE
A UNIQUE CLUSTER ADDRESS
1,2,3,4 ETC.
ZMGRSWP3.CDR 3/6/00
Remember
- You must power down the Zone
Manager after changing the address switches
in order for any changes to take effect.
CLUSTER ADDRESS SWITCH
NETWORK SWITCH
IS ALWAYS "ON"
RIBBON CABLE MUST BE CONNECTED
NOT USED
NETWORK SWITCH MUST
BE IN OFF POSITION
IN ORDER FOR
MINILINK TO
FUNCTION
Figure 2-6:
Zone Manager Address Switch Setting
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...