Section 2
Auto-Zone
Plus
2-36
Design Guide
System Manager Wiring
The System Manager can be connected anywhere on the Plus system local
communications loop.
Do Not Connect the System Manager to the Plus System
Network Loop!
The system will not function if the System Manager is connected to the
network loop. The System Manager must also be connected to 24 VAC in order to
operate. See
Figure 2-29
for System Manager wiring.
Figure 2-29:
System Manager Wiring
Notes:
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
3.) All Communication Wiring To Be
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Equivalent.
Line Voltage
See Note 1
See Note 3
24VAC
GND
Required VA For Transformer
System Manager = 25VA Max.
MADE IN
THE USA
EPROM
1000uF10v
YS101806 REV. 1
DSPY1
UNIVERSAL SMART DISP. UNIT
SYSTEM MANAGER
SERIAL # :
U13
SERIAL #
1000uF10v
C9
470uF50v
D2
PCB80C552-5-16WP
442860=2/5
DfD9722V7
Y
PHILIPS
CX13
LD8
CX9
SS0017
vx.xx 1234
V62C518256L-70P
U9
U8
LD7
RN1
LD6
U7
CX7
74HC573
LD5
LD4
74HC573
CX8
RN2
X2
CX4
470uF50v
TB2
GND
24V
AC
R10
75176
RS-485
COMM
U12
CX12
RAM
SC1
T
TB1
SHLD
C7
C1
1
L1
C4
R
D6
8583
U6
CX6
C3
D3
24C128
U5
R7
VAR1
D4
PJ1
R3
U1
74HC259
LD3
LD2
LD1
R2
R1
EWDOG
PHILIPS
U3
U2
CX1
82B715
CX5
CX3
U3
DSPY1
R5
D1
R6
MC34064A
C6
R11
9936
C8
R9
U10
U11
R8
R12
C5
74HC923
CX10
P1
R4
RV1
C2
C1
X1
System Manager Cover
System Manager Base
The Ideal Recommended Location For The System Manager Is As The First
Device On The Local Loop. The System Manager May Be Connected To The
Local Loop At Any Point On The Local Loop.
Connect To Any Controller On
The Local Loop
Do Not Connect To The
Network Loop !
6
5
4
DEC
7
MINUS
0
CLEAR
9
8
1
3
2
MENU
Override
Communication
ENTER
ESC
Alarm
firealarmresources.com
Содержание Auto-Zone Plus
Страница 1: ...Design Installation And Operations Manual Plus System Revision 02B firealarmresources com...
Страница 2: ...firealarmresources com...
Страница 4: ...firealarmresources com...
Страница 6: ...firealarmresources com...
Страница 68: ...firealarmresources com...
Страница 116: ...firealarmresources com...
Страница 124: ...Section 4 Auto Zone Plus 4 6 Start Up and Troubleshooting Figure 4 4 Local Loop Wiring firealarmresources com...
Страница 155: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 37 Notes firealarmresources com...
Страница 177: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 59 Notes firealarmresources com...
Страница 178: ...Section 4 Auto Zone Plus 4 60 Start Up and Troubleshooting Notes firealarmresources com...
Страница 179: ...Auto Zone Plus Section 4 Start Up and Troubleshooting 4 61 Notes firealarmresources com...