Installing the Tank Level—Sensor Cable
1. Connect the sensor wires to the wires on the foam concentrate sensor.
2. Remove the cover. Refer to
"Removing the Cover" on page 56
.
3. Secure one wire to terminal 3 and the other wire to terminal 5 on the
terminal strip (
Note:
Add the appropriate connectors as required by your application.
Figure 49
4. Install the cover. Refer to
"Installing the Cover" on page 59
.
5.
Loop the excess cable by bringing 2 sides of the loop together to flatten it
).
6.
Use a cable tie to secure the excess cable into a flat loop (
).
Note:
Use the previous instructions to install a second tank level sensor
to the controller. Connect the wires from the sensor to terminals 2
and 5 on the terminal strip.
Installing the Wye Fitting with Strainer
The wye fitting with strainer is installed in-line with the supply shutoff valve and
the supply hose. The wye fitting can be hard plumbed to the tank shutoff valve,
it may be remotely mounted, or mounted to the intake of the foam pump.
1.
Determine a location to install the wye fitting with strainer that is accessible
for maintenance.
2.
Use the arrow on the body of the wye strainer to determine the flow
direction of the foam concentrate (
).
Figure 50
3. Make sure that the stainer feature is pointing down.
4.
Secure the wye fitting to the apparatus.