64
|
90
Safety Introduction Product Overview
11.
Use the following chart to determine your flow rate.
Default mix percentage
0.1% 0.2% 0.3% 0.4% .05% 0.6% 0.7% 0.8% 0.9% 1.0%
Fl
ow r
at
e
U
S g
al
lon
s
100
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
200
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
300
0.3
0.6 0.9
1.2
1.5
1.8
2.1
2.4
2.7
3.0
12. Enter the calibration mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
13. Navigate to
(F6 parameter).
14. Press the
(SELECT button) to edit the parameter.
15. Use the
(down button) to display the
(zero
flow).
16. Press the
(SELECT button) to save the value.
17. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
Setting Default Mix Percent for B Foam—F7
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
2. Navigate to
(F7 parameter).
3. Press the
(SELECT button) to edit the parameter.
4. Use the
or
(up or down button) to display the desired
foam percent.
The value displayed is
(1.0 percent),
(3.0 percent), or
(6.0 percent).
5. Press the
(SELECT button) to select the displayed value.
6. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
Auto Run Mode
Apply voltage (+12 Vdc or +24 Vdc) to terminal 1 on the accessory terminal strip
to enable run mode. Refer to: