The electrical requirements vary based on your specific application. The
following tables are calculated using the SAE J1128 standard with a 2% drop.
12 V
Length of Wire
10 ft
15 ft
20 ft
25 ft
30 ft
A
mp
s
50 A
6 AWG
4 AWG
2 AWG
2 AWG
2 AWG
80 A
4 AWG
2 AWG
1 AWG
0 AWG
0 AWG
100 A
2 AWG
2 AWG
0 AWG
00 AWG
00 AWG
24 V
Length of Wire
10 ft
15 ft
20 ft
25 ft
30 ft
A
mp
s
30 A
12 AWG
10 AWG
8 AWG
8 AWG
6 AWG
50 A
8 AWG
8 AWG
6 AWG
4 AWG
4 AWG
80 A
6 AWG
6 AWG
4 AWG
2 AWG
2 AWG
Important:
The foam pump requires a frame ground.
Important:
Make sure that you use the same gauge for the ground cable
as you use for the power cable.
1. Remove the cover. Refer to:
"Removing the Cover" on page 56
.
2. Route the positive (+) cable from the power source to the foam pump.
3. Connect one end of the positive (+) cable to the Vdc source.
4. Connect the other end of the positive (+) cable to the positive (+) post of the
foam pump (
1
2
1. Positive (+) post
2. Negative (–) post
Figure 48
5. Connect the negative (–) post to the frame ground.
6. Install the cover. Refer to: