WAGO-I/O-SYSTEM 750
System Description 23
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
3.5.3
System Supply
3.5.3.1 Connection
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply.
The power supply is provided via the fieldbus coupler/controller and, if necessary,
in addition via internal system supply modules 750-613. The power supply is
reverse voltage protected.
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to
the components.
Figure 6: System Supply via Fieldbus Coupler/Controller (left) and via Internal System Supply
Module (right)
Table 4: Legend for Figure “System Supply via Fieldbus Coupler/Controller (left) and via Internal
System Supply Module (right)”
Position Description
1
System supply DC 24 V (-25 % … +30 %)
2
System supply 0 V
The fed-in 24 VDC supplies all internal system components, e.g. fieldbus
coupler/controller electronics, fieldbus interface and I/O modules via the local bus
(5 VDC system voltage). The 5 VDC system voltage is galvanically connected to
the 24 VDC supply voltage.