10.2.8 Type 6 - 2-channel digital input; Acknowledgement;
Diagnostics
Occupied input process image [(channel x) bits]:
(1x) 4
Occupied output process image [(channel x) bits]: (1x) 4
Items that use this mapping type:
0750-0418
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Digital input
I
0
1
BOOL
Digital input
I
0
2
BOOL
Diagnostic
I
0
3
BOOL
Diagnostic
Q
0
2
BOOL
Reset diagnostic
Q
0
3
BOOL
Reset diagnostic