10.2.6 Type 4 - Frequency Counter type 1
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0404/0000-0003
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Frequency measuring range
I
0
1
BOOL
Frequency measuring range
I
0
2
BOOL
Status out 1
I
0
3
BOOL
Status out 2
I
0
4
BOOL
Tvd Acknowledge
I
0
5
BOOL
Status Gate input
I
2
WORD
Frequency Low Word
I
4
WORD
Frequency High Word
Q
0
0
BOOL
Acknowledgment frequency range
Q
0
1
BOOL
Acknowledgment frequency range
Q
0
2
BOOL
Control out 1
Q
0
3
BOOL
Control out 2
Q
0
4
BOOL
Tvd Request
Q
2
WORD
Watchdog Time
10.2.7 Type 5 - 2 up counter; 16 bits
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0404/0000-0005
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Status clock
I
0
1
BOOL
Status up/down
I
0
2
BOOL
Status out 1
I
0
3
BOOL
Status out 2
I
0
4
BOOL
Status bit accept set value 2
I
0
5
BOOL
Status bit accept set value 1
I
2
WORD
Actual count value 1
I
4
WORD
Actual count value 2
Q
0
2
BOOL
control out 1
Q
0
3
BOOL
control out 2
Q
0
4
BOOL
Control bit accept set value 2
Q
0
5
BOOL
Control bit accept set value 1
Q
2
WORD
set count value 1
Q
4
WORD
set count value 2