126 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.17 Type 15 - SSI transmitter interface
Occupied input process image [(channel x) bits]:
(1x) 32
Occupied output process image [(channel x) bits]: -
Items that use this mapping type:
0750-0630, 0750-0630/0000-0001, 0750-0630/0000-0002,
0750-0630/0000-0004, 0750-0630/0000-0005, 0750-0630/0000-0006,
0753-0630/0000-0006, 0750-0630/0000-0007, 0750-0630/0000-0008,
0750-0630/0000-0009, 0750-0630/0000-0011, 0750-0630/0000-0012,
0750-0630/0000-0013, 0750-0630/0003-0000
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
WORD
Actual value Low Word
I
2
WORD
Actual value High Word
10.2.18 Type 16 - Incremental encoder interface type 1
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0631
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Latched Data Set
I
0
1
BOOL
External Latch Ack.
I
0
2
BOOL
Counter Set Acknowledge
I
0
3
BOOL
Counter Underflow
I
0
4
BOOL
Counter Overflow
I
1
BYTE
Counter value Low Byte
I
2
BYTE
Counter value High Byte
I
4
WORD
Latch value
Q
0
0
BOOL
Release Index Pulse
Q
0
1
BOOL
Release Latch
Q
0
2
BOOL
Counter Set
Q
1
BYTE
Set value Low Byte
Q
2
BYTE
Set value High Byte