134 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.27 Type 25 - Digital input; Diagnostics
Occupied input process image [(channel x) bits]:
(2x) 2
Occupied output process image [(channel x) bits]: -
Items that use this mapping type:
0750-0424, 0750-0435
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Digital Input
I
0
1
BOOL
diagnostic
10.2.28 Type 26 - 1-channel digital output
Occupied input process image [(channel x) bits]:
(1x) 2
Occupied output process image [(channel x) bits]: (1x) 2
Items that use this mapping type:
0750-0523, 0750-0523/0010-0000
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Diagnostic bit
Q
0
0
BOOL
Digital output
10.2.29 Type 28 - 12 Bytes Generic IN/OUT
Occupied input process image [(channel x) bits]:
(1x) 96
Occupied output process image [(channel x) bits]: (1x) 96
Items that use this mapping type:
0750-0644#12, 0750-0655#12, 0753-0655#12, 0750-0657#12, 0750-0658#12
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
First Byte of 12
Q
0
0
BYTE
First Byte of 12