90 Commissioning
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
8.1
Connecting Fieldbus Node
1. Install the assembled fieldbus node on the DIN rail. Observe the installation
instructions (see “Mounting” section).
2. Connect the 24v power supply to the supply module
(see “System Description” >> “Power Supply” and the section “Connect
Devices”).
3. Connect your controller with the CC-Link interface of the fieldbus coupler
(see section “Device Description” >> “Connectors” >> “Fieldbus Connection”).
8.2
Setting and Switching On Fieldbus Couplers
1.
Use the rotary encoder switches to set the required station address
(see section “Device Description” >> “Operating Elements” >> “Rotary
Encoder Switch Station Address”).
2.
Use DIP switches 1/2/3 to set the required baud rate
(see “Device Descriptions” >> “Operating Elements” >> “DIP Switch”).
3.
Based on the I/O modules in the fieldbus nodes used, determine the size of
the process images for the input and output data
(see section “Function Description” >> “Process Data Architecture” and
“Data Exchange” as well as the section “I/O Modules”).
4.
Use DIP switches 4/5 to set the number of occupied station addresses
according to the determined process image sizes and use DIP switches 6/7
for extended cyclic setting
(see section “Device Description” >> “Operating Elements” >> “DIP
Switch”).
5.
Turn the operating voltage on.