52 Device Description
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
4.4.3.2 Extended Cyclic Setting
The extended cyclic setting is set via pins 6 and 7 of the DIP switch. This setting
is only possible with CC-Link V 2.0.
Table 18: Extended Cyclic Setting
Pin Value Setting
6/7
0/0
1 cycle
1/0
2 cycles
0/1
*)
4 cycles
1/1
8 cycles
*)
default setting
4.4.3.3 Occupied Stations
The number of occupied stations is set via pins 4 and 5 of the DIP switch.
Table 19: Occupied Stations Setting
Pin Value Setting
4/5
0/0
1 station
1/0
2 stations
0/1
3 stations
1/1
*)
4 stations
*)
default setting
4.4.3.4 Baud Rate
The baud rate is set via pins 1 til 3 of the DIP switch.
Table 20: Baud Rate Setting
Pin Value Setting
1/2/3 0/0/0 156 kBaud
1/0/0 625 kBaud
0/1/0 2.5 MBaud
1/1/0 5 MBaud
0/0/1
*)
10 MBaud
1/0/1
Invalid setting
0/1/1
1/1/1
*)
default setting