WAGO-I/O-SYSTEM 750
Function Description 85
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
Table 46: Example Data Transfer Type 13
Link Input
Signal name high
byte
low
byte
Link Output
Signal name
high
byte
low
byte
RWrn(k)
Channel 1
Status byte S0/
Channel 1
Data byte D0
D0
S0
RWwn(k)
Channel 1
Control byte C0/
Channel 1
Data byte D0
D0
C0
RWrn(k+1)
Channel 1
Data byte D1/
Channel 2
Status byte S1
S1
D1 RWwn(k+1)
Channel 1
Data byte D1/
Channel 2
Control byte C1
C1
D1
RWrn(k+2)
Channel 2
Data bytes
D2/3
D3
D2 RWwn(k+2)
Channel 2
Data bytes
D2/3
D3
D2
7.3.2.6.3 Example
In this example the remote station consists of:
•
1 x 750-325
CC-Link fieldbus coupler,
•
2 x 750-400
2-channel digital input module (DI) / Type 1,
•
4 x 750-504
4-channel digital output module (DO) / Type 10,
•
2 x 750-467
2-channel analog input module (AI) / Type 8,
•
1 x 750-550
2-channel analog output module (AO) / Type 14,
•
1 x 750-506
2-channel digital output module (DO/DIAG) / Type 11
•
1 x 750-418
2-channel digital input module (DO/DIAG/Ack)/Type 6
•
1 x 750-404
Counter module /Type 2
•
1 x 750-600
End module
The CC-Link fieldbus coupler is parameterized by means of DIP switches as
follows:
Table 47: Example – DIP Switch Setting
Pin value Setting
8
1
*)
Operation mode
CC-Link V 2.0
*)
6/7
0/0
Extended cyclic
setting
1
4/5
1/0
Occupied stations
2
1/2/3 0/0/1
*)
Baud rate
10 MBaud
*)
*)
default setting