144 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
I/Q
Byte
Bit
Data Type
Contents
Q
10
1
BOOL
Speed divider Bit 1
Q
10
2
BOOL
CTL ACC FAC BIT0
Q
10
3
BOOL
CTL ACC FAC BIT1
Q
10
6
BOOL
Save Value
Q
10
7
BOOL
Quit Error
Q
11
0
BOOL
Enable Module
Q
11
1
BOOL
0 = stop drive, inverted signal
Q
11
2
BOOL
0->1 starts drive
Q
11
3
BOOL
single positioning, MBX must be inactive
Q
11
4
BOOL
Program Mode
Q
11
5
BOOL
Reference Mode
Q
11
6
BOOL
Jog Mode
Q
11
7
BOOL
Mailbox Mode
10.2.46 Type 46 - VIB I/O
Occupied input process image [(channel x) bits]:
(4x) 24
Occupied output process image [(channel x) bits]: (4x) 24
Items that use this mapping type:
0750-0645
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
BYTE
Status byte
I
1
BYTE
Input word Low Byte
I
2
BYTE
Input word High Byte
Q
0
BYTE
Control byte
Q
1
BYTE
Output word Low Byte
Q
2
BYTE
Output word High Byte
10.2.47 Type 47 - 3-Phase Power Measurement type 1
Occupied input process image [(channel x) bits]:
(3x) 32
Occupied output process image [(channel x) bits]: (3x) 32
Items that use this mapping type:
0750-0493, 0750-0493/0000-0001, 0750-0639
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
Status byte
I
2
0
BYTE
Input word Low Byte
I
3
0
BYTE
Input word High Byte
Q
0
0
BYTE
Control byte
Q
2
0
BYTE
Output word Low Byte
Q
3
0
BYTE
Output word High Byte