76 Function Description
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
The following table describes the system area flags.
Table 33: System Area Flags
System Area-Flags
Description
RX(m+n)8
Initial data processing request flag
Used when the fieldbus coupler requests the
initial processing to the master after the power
supply of the fieldbus coupler is switched on or
after a hardware reset.
RY(m+n)8
Initial data processing complete
flag
RX(m+n)9
Initial data setting complete flag
Used when the master requests the initial setup
to the fieldbus coupler.
RY(m+n)9
Initial data setting request flag
RX(m+n)A
Error status flag
Used when the fieldbus coupler notifies an error
other than watchdog timer errors.
RY(m+n)A
Error reset request flag
RX(m+n)B
Remote station ready flag
Used to notify the completion of the initial
processing for the initial data setup.
The position of the system area and the size of the usable data area depend on
the selected CC-Link configuration. In analogy to the above data range
representation of the remote I/Os, these can be derived from the following
position tables, respectively, according to the number of extended cycle settings
and occupied stations.
Table 34: Position of Remote I/O System Area V1.1 or V2.0 at the Setting of one Cycle
RX/RY
Number of occupied Stations at the Setting of one Cycle
1
2
3
4
00 – 0F
User Area
User Area
User Area
User Area
10 – 1F
System Area
User Area
User Area
User Area
20 – 2F
(cannot be used)
User Area
User Area
User Area
30 – 3F
System Area
User Area
User Area
40 – 4F
(cannot be used)
User Area
User Area
50 – 5F
System Area
User Area
60 – 6F
(cannot be used)
User Area
70 – 7F
System Area