130 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.22 Type 20 - Up/down counter 16 bits
Occupied input process image [(channel x) bits]:
(2x) 24
Occupied output process image [(channel x) bits]: (2x) 24
Items that use this mapping type:
0750-0638
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Overflow locked/allowed
I
0
1
BOOL
Counter up/down
I
0
4
BOOL
Counter locked/count
I
0
5
BOOL
Counter (set and hold)/mode
I
1
BYTE
Counter value Low Byte
I
2
BYTE
Counter value High Byte
Q
0
0
BOOL
Lock overflow
Q
0
1
BOOL
Set counter mode forward/backwards
Q
0
4
BOOL
Set counter lock/count
Q
0
5
BOOL
Set counter with the set value/counting made
Q
1
BYTE
Set value Low Byte
Q
2
BYTE
Set value High Byte