WAGO-I/O-SYSTEM 750
I/O Modules 129
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.21 Type 19 - Incremental encoder interface type 3
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0637, 0750-0637/0000-0001, 0750-0637/0000-0002, 0750-0637/0000-0003
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Confirmation of initial point activation
I
0
1
BOOL
External Latch Ack.
I
0
2
BOOL
Counter Set Acknowledge
I
0
3
BOOL
Counter Underflow
I
0
4
BOOL
Counter Overflow
I
0
5
BOOL
Counter Set Acknowledge
I
1
BYTE
IN Data Value Byte 0
I
2
BYTE
IN Data Value Byte 1
I
3
0
BOOL
State process data coding Bit 0
I
3
1
BOOL
State process data coding Bit 1
I
3
2
BOOL
State Cam 1
I
3
3
BOOL
State Cam 2
I
3
4
BOOL
Cam 1 active
I
3
5
BOOL
Cam 2 active
I
4
BYTE
IN Data Value Byte 2
I
5
BYTE
IN Data Value Byte 3
Q
0
0
BOOL
Release Index Pulse
Q
0
1
BOOL
Releas Latched Data
Q
0
2
BOOL
Counter Set
Q
0
3
BOOL
Underflow Reset
Q
0
4
BOOL
Overflow Reset
Q
0
5
BOOL
Set load external
Q
0
6
BOOL
Operation mode
Q
1
BYTE
IN Data Set Value Byte 0
Q
2
BYTE
IN Data Set Value Byte 1
Q
3
0
BOOL
Code Process Data
Q
3
1
BOOL
Code Process Data
Q
3
2
BOOL
Disable Cam 1
Q
3
3
BOOL
Disable Cam 2
Q
3
4
BOOL
Cam 1 set comparison values
Q
3
5
BOOL
Cam 2 set comparison values
Q
3
6
BOOL
Input REF Set
Q
4
BYTE
IN Data Set Value Byte 2
Q
5
BYTE
IN Data Set Value Byte 3