Troubleshooting the Blower
Cub 200/300
32
ghi_tx001207gb.fm
Continued from the previous page.
5. Measure the voltage between terminal
M8
and terminal
M11
on the control
board.
Is 108–132 VAC measured?
6. Measure the voltage between terminal
M15
and terminal
M14
.
Is 108–132 VAC measured?
Result
The power to and from the control board has now been checked.
If the problem has not been resolved, leave the machine disassembled and
continue with the next topic. Otherwise, reassemble the machine.
Yes ____
No ____
Continue.
Disconnect the power supply. Check the function of the ON-OFF
switch and the wiring to the ON-OFF switch.
Yes ____
No ____
The power to and from the control board is
OK.
The control board has failed. Disconnect
the power supply and replace the control
board.