Burner Setup
Cub 200/300
20
ghi_tx001317gb.fm
Continued from the previous page.
8. Analyze the combustion. Follow the combustion analyzer manufacturer’s
instructions and the general guidelines below.
Use the access hole in the exhaust stack.
Take several samples as the heater warms.
Take the final sample just before the heater reaches 71°C (160°F).
9. Re-adjust the air band, if necessary, until the smoke spot test and combustion
analysis are within the following parameters:
O
2
content: 3–5%
Smoke spot: less than 1
Result
The burner has now been set.