17 Technical data
41
100_0102_td_0007.fm
17.1.1
Extension cable
The following points must be observed:
Only use permitted extension cables.
Refer to nameplate for details of type designation and voltage of this machine.
Refer to the following table for the required cross-section area.
WARNING
Warning about voltage.
Serious injuries from electric shock.
Check power cable and extension cable for signs of damage.
Only use extension cables for which grounded conductors are connected to the plug
and the coupling (only for machines of protection class I + III, see chapter "Technical
data").
Machine type
Voltage
[V]
Extension
[m] (ft)
Cross-section area of
cable
[mm
2
]
AR43/3/230 v
230 1~
< 150 (492.1)
1.5
AR43/3/400
400 3~
< 150 (492.1)
1.5
AR43/6/042
42 3~
< 10 (32.8)
1.5
< 17 (55.8)
2.5
< 27 (88.6)
4
< 39 (128.0)
6
< 61 (200.1)
10
AR43/6/250
250 3~
< 150 (492.1)
1.5
Machine type
Voltage
[V]
Extension
[m] (ft)
Cross-section area of
cable
[AWG]
AR43/3/230 v
230 3~
< 150
16
AR43/3/400
400 3~
< 150
16
AR43/6/042
42 3~
< 9
16
< 14
14
< 22
12
< 34
10
< 52
8
AR43/6/250
250 3~
< 150
16