20 Technical data
55
100_0102_td_0008.fm
The following points must be observed:
Only use permitted extension cables.
Refer to nameplate for details of type designation and voltage of this machine.
Refer to the following table for the required cross-section area.
Machine type
Voltage
[V]
Extension
[m] (ft)
Cross-section area of
cable
[mm
2
]
AR75/1,5/400
400 3~
< 150 (492.1)
1,5
AR75/3/230 v
0-400 3~
< 150 (492.1)
1,5
AR75/3/400
400 3~
< 150 (492.1)
1,5
AR75/6/042
42 3~
< 10 (32.8)
4
< 14 (45.9)
6
< 23 (75.5)
10
AR75/6/250
250 3~
< 99 (324.8)
1,5
< 150 (492.1)
2,5
AR75/9/042
42 3~
< 12 (39.4)
4
< 17 (55.8)
6
< 27 (88.6)
10
AR75/9/250
250 3~
< 150 (492.1)
1,5
Machine type
Voltage
[V]
Extension
[m] (ft)
Cross-section area of
cable
[AWG]
AR75/1,5/400
400 3~
< 150 (492.1)
16
AR75/3/230 v
0-400 3~
< 150 (492.1)
16
AR75/3/400
400 3~
< 150 (492.1)
16
AR75/6/042
42 3~
< 13 (42.7)
10
< 20 (65.6)
8
AR75/6/250
250 3~
< 86 (282.2)
16
< 135 (442.9)
14
< 150 (492.1)
12
AR75/9/042
42 3~
< 15 (49.2)
10
< 23 (75.5)
8
AR75/9/250
250 3~
< 150 (492.1)
16