4.5 - GREEN MACHINE
™
- North America - Installation, Operation, Maintenance, & Troubleshooting Manual
Chapter 6: Testing and Startup
Page 93
6.9
Submitting Appendix B to VST for the Verification CODE
6.9.1
Start Up of the GREEN MACHINE
1. Go to www.vsthose.com
2. Click on VST Education
3.
Under “North America GREEN MACHINE,”
Click on “Supporting Documents and Instructional Video”
4.
Click on “Start
-
Up/Commissioning Contractor.”
5.
Click on “Appendix B –
Start-
Up Contractor Check Out Form.”
6. Fill out and submit Appendix B with the required photos.
7. Receive an email from VST with the Verification CODE and a copy of the filled-out Appendix B
6.9.2
Procedures
1.
Apply power to the VST Control Panel
The PLC starts up in the Main Screen where the GREEN MACHINE is shown to be DISABLED.
See
Figure 6-1.
2.
Push the Maintenance button, then enter 878 on the Password Screen to go to the Maintenance
Screen.
3.
Using Chapter 6: Testing and Start-Up, complete the following sections:
Chapter 6 Sections for Reference:
Section Title
6.4 Conduct the Bump Test
6.5 Conduct the Functionality Test
6.6 Programming the Fuel Management System Overfill Relay for the GM Overfill Alarm
6.7 Conduct the Overfill Alarm Test
6.8 Change the Date/Time per the time-zone
6.9 How to submit Appendix B to VST to obtain the Verification CODE
4.
Complete Appendix B Checklist Form, then push the SUBMIT button.
(All the fields contained in Appendix B MUST BE CHECKED OR FILLED OUT, INCLUDING PICTURES.
5.
An email with the Verification CODE is sent to the person conducting the Start-Up after Appendix B
is SUBMITTED to VST.
6.
On the Maintenance Screen, push the Function Buttons F1 & F2 at the same time to bring up the
Password Screen to enter the Verification CODE.
7.
Push the large button with 000000 showing.
See Figure 6-14
.
8.
At the Verification CODE Screen, enter the CODE that was received in the email, then push ENTER.
See Figure 6-15.
9.
If the correct CODE was entered, the PLC will show the Main Screen and the GREEN MACHINE will
now be operational.
10.
If the incorrect CODE is entered, the Verification CODE Screen will show WRONG! Push the large
button again and enter the correct Verification CODE.
11.
Once the correct Verification CODE is entered, the PLC returns to the Main Screen and the GREEN
MACHINE is now fully operational.
12.
Function Buttons F1 & F2 will no longer work
13.
At the Main Screen, the GREEN MACHINE will turn ON if the UST pressure is at or above 0.20 IWC,
or remain OFF if the UST pressure is below 0.20 IWC.
14.
The GREEN MACHINE:
•
Is Operational
•
Start-Up is complete and verified
•
The Overfill protection is installed and tested