Fault code
on the dis-
play
System character-
istics
Cause
Measures
FE
Burner blocked
Strong interfer-
ence (EMC) field
nearby or boiler
coding card/main
PCB faulty
Check boiler coding
card, restart the equip-
ment. Replace the con-
trol unit if the equipment
will not restart.
FF
Burner blocked
Internal fault
Start the equipment
again. Replace the con-
trol unit if the equipment
will not restart.
Repairs
Checking the outside temperature sensor (weather-compen-
sated control unit)
1.
Pull plug "X3" from the control unit.
Fault codes
(cont.)
74
Troubleshooting
5692
779
GB