Please note
When selecting a value below 1 °C, there is a risk of pipes outside the
thermal envelope of the building being damaged by frost.
The standby mode, in particular, should be taken into consideration, e.g.
during holidays.
Parameter
Heating circuit pump
Address A3: ...
"ON" at
"OFF" at
-9
-10 °C
-8 °C
-8
-9 °C
-7 °C
-7
-8 °C
-6 °C
-6
-7 °C
-5 °C
-5
-6 °C
-4 °C
-4
-5 °C
-3 °C
-3
-4 °C
-2 °C
-2
-3 °C
-1 °C
-1
-2 °C
0 °C
0
-1 °C
1 °C
1
0 °C
2 °C
2
to
1 °C
to
3 °C
15
14 °C
16 °C
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A4:0
With frost protection
A4:1
No frost protection, ad-
justment only possible if
coding address "A3: -9"
has been selected.
Note
Observe the note for
code "A3"
Code 2
(cont.)
54
Coding
5692
779
GB