External heating program changeover
The "External heating program chan-
geover" function is connected via
external extension input "
aVD
". You
can select which heating circuits the
heating program changeover affects
in coding address "91":
Heating program changeover
Coding
No changeover
91:0
Heating circuit without mixer A1
91:1
Heating circuit with mixer M2
91:2
Heating circuit without mixer and heating circuit with mixer 91:3
You can select in which direction the
heating program changes over in cod-
ing address "D5":
Heating program changeover
Coding
Changeover towards "Permanently reduced" or "Perma-
nent standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Heating program changeover
Coding
No heating program changeover
F2:0
Duration of the heating program changeover 1 to 12 hours
F2:1 to
F2:12
The heating program changeover
stays enabled for as long as the con-
tact remains closed, but at least as
long as the duration selected in cod-
ing address "F2".
Control functions
87
Function description
5692
779
GB
Содержание VITOLADENS333-F
Страница 96: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 96 Designs 5692 779 GB...
Страница 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Страница 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Страница 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Страница 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Страница 105: ...Parts lists cont 105 Parts lists 5692 779 GB...