Coding in the delivered condition
Possible change
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card.
Observe the max. per-
missible DHW tempera-
ture.
58:0
Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW temperature, adjus-
table from 10 to 60 °C
(observe coding ad-
dresses "56" and "63")
59:0
Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the
set value
60:20
During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than the set
DHW temperature
60:5
to
60:25
The difference between
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:2
Circulation pump with
2 min run-on time after
cylinder heating
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
65:...
Information regarding
the type of diverter
valve. Do not adjust
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
6C:100
Set speed; internal cir-
culation pump with
DHW heating 100 %
6C:0
to
6C:100
Set speed adjustable
from 0 to 100 %
Code 2
(cont.)
50
Coding
5692
779
GB
Содержание VITOLADENS333-F
Страница 96: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 96 Designs 5692 779 GB...
Страница 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Страница 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Страница 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Страница 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Страница 105: ...Parts lists cont 105 Parts lists 5692 779 GB...