Calling up code 1
Note
Codes are displayed as plain text.
Codes that are irrelevant (due to the
heating system equipment level or the
setting of other codes) will not be dis-
played.
Press the following keys:
1.
K
+
L
simultaneously for
approx. 2 s.
2.
a
/
b
for the required coding
address; the address
flashes
3.
d
to confirm
4.
a
/
b
for the selected value
5.
d
to confirm; the display
briefly shows "
accepted
"
(weather-compensated
control unit); the address
flashes again.
6.
a
/
b
for the selection of further
addresses.
7.
K
+
L
approx. 1 s simulta-
neously, to terminate
coding 1.
Overview
Coding
Coding in the delivered condition
Possible change
System design
00 :2
System design 2:
1 heating circuit without
mixer A1, with DHW
heating
00 :4
System design 2 and 5:
1 heating circuit with
mixer M2, with DHW
heating
00 :6
System design 3, 4:
1 heating circuit without
mixer A1; 1 heating cir-
cuit with mixer M2, with
DHW heating
Max. boiler water temp.
06:...
Maximum limit of the
boiler water tempera-
ture, defaulted by the
boiler coding card
06:20
to
06:127
Maximum limit of the boil-
er water temperature
within the ranges de-
faulted by the boiler
Code 1
43
Coding
5692
779
GB
Содержание VITOLADENS333-F
Страница 96: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 96 Designs 5692 779 GB...
Страница 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Страница 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Страница 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Страница 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Страница 105: ...Parts lists cont 105 Parts lists 5692 779 GB...